a. Only approved safety cans, original containers, or portable tanks will be used to store flammable or combustible liquids. b. Above ground storage tanks will be separated from each other by a minimum of three feet or 1/6 the sum of their diameters. Dikes or drainage to prevent accidental discharge from reaching adjoining property or waterways will be provided. c. No more than 25 gallons of Class IA and 120 gallons of Class IB, IC, II, or III liquids may be stored outside a storage cabinet or an inside storage room. d. An emergency shut off switch located 15 - 75 feet from the pumps and a fire extinguisher will be provided at company fuel servicing areas. |

| H E A L T H A N D S A F E T Y P R O G R A M |


| Flammable And Combustible Liquids |
| Houston KACO, Inc. 7107 Peerless Street Houston, TX 77021 (713) 203-2505 |